Description
UL555 Certified Airfoil blades Leakage Class 1 Fire Smoke Damper
1 1/2 hrs rated, UL555 certified leakage class 1 fire smoke dampers – with or without actuator
Make: Greenheck India
Model: FSD311
UL555 Certified Fire Smoke Damper model FSD-311 is a high performance combination fire smoke damper with Class I leakage with 1 1/2 hrs fire resistance rating. High strength airfoil blades ensure the lowest resistance to airflow in HVAC systems with velocities to 4000 fpm (20.3 m/s) and pressures to 8 in. wg (2 kPa).
FSD-311 is available with high performance, fast acting spring return electric actuator / motor with fail-safe function and auxiliary switch for position indication. Actuator can be offered with 24V AC / DC or 230V AC power supply option.
Model FSD-311 may be installed vertically (with blades running horizontal) or horizontally and is rated for airflow and leakage in either direction.
Model FSD-311 meets the requirements for fire dampers, smoke dampers and combination fire smoke dampers established by:
- National Fire Protection Association NFPA Standards 80, 90A, 92A, 92B, 101 & 105
- IBC International Building Codes
- New York City (MEA listing #260-91-M)
- CSFM California State Fire Marshal
- Fire Damper Listing (#3225-0981:103)
- Leakage (Smoke) Damper Listing (#3230-0981:104)
Key Features:
- UL 555 Fire Resistance Rating
- Fire Rating: 11⁄2 hours
- Dynamic Closure Rating: Actual ratings are size dependent
- Velocity: Up to 4,000 fpm (20.3 m/s)
- Pressure: Up to 8 in. wg (2 kPa)
- UL 555S Leakage Rating
- Leakage Class: I
- Operational Rating: Actual ratings are size dependent
- Velocity: Up to 4,000 fpm (20.3 m/s)
- Pressure: Up to 8 in. wg (2 kPa)
- Temperature: Up to 350°F (177°C) – depending upon the actuator
- Frame Material : Galvanized steel
- Frame Material Thickness : 16 ga. (1.5mm)
- Blade Material: Galvanized steel
- Blade Material Thickness: 14 ga. (2mm) equivalent
- Blade Type : Airfoil
- Linkage : Plated steel out of airstream, concealed in jamb
- Axle Bearings : 304SS
- Axle Material: Plated steel
- Blade Seals: Silicone
- Jamb Seals : 304SS
- Closure Device : RRL, Optional: RRL/OCI, TOR
- Closure Temperature: 165°F (74°C)
Typical Ventilation Applications area include:
- Enclosed / Basement air and smoke ventilation
- Smoke / Fire Curtain, Zoning
- Building fire separation